Chlorodifluoromethane

Chlorodifluoromethane or difluoromonochloromethane is a hydrochlorofluorocarbon (HCFC). This colorless gas is better known as HCFC-22, or R-22, or CHClF
2
. It is commonly used as a propellant and refrigerant. These applications are being phased out in developed countries due to the compound's ozone depletion potential (ODP) and high global warming potential (GWP), although global use of R-22 continues to increase because of high demand in developing countries.[2] R-22 is a versatile intermediate in industrial organofluorine chemistry, e.g. as a precursor to tetrafluoroethylene.

Chlorodifluoromethane
Names
Preferred IUPAC name
Chloro(difluoro)methane
Other names
Chlorodifluoromethane
Difluoromonochloromethane
Monochlorodifluoromethane
HCFC-22
R-22
Genetron 22
Freon 22
Arcton 4
Arcton 22
UN 1018
Difluorochloromethane
Fluorocarbon-22
Refrigerant 22
Identifiers
3D model (JSmol)
ChEMBL
ChemSpider
ECHA InfoCard 100.000.793
EC Number
  • 200-871-9
KEGG
RTECS number
  • PA6390000
UNII
Properties
CHClF2
Molar mass 86.47 g/mol
Appearance Colorless gas
Odor Sweetish[1]
Density 3.66 kg/m3 at 15 °C, gas
Melting point −175.42 °C (−283.76 °F; 97.73 K)
Boiling point −40.7 °C (−41.3 °F; 232.5 K)
0.7799 vol/vol at 25 °C; 3.628 g/L
log P 1.08
Vapor pressure 908 kPa at 20 °C
0.033 mol⋅kg−1⋅bar−1
−38.6·10−6 cm3/mol
Structure
Tetrahedral
Hazards
Main hazards Dangerous for the environment (N), Central nervous system depressant, Carc. Cat. 3
GHS pictograms
GHS Signal word Warning
GHS hazard statements
H280, H420
P202, P262, P271, P403
NFPA 704 (fire diamond)
Flammability code 0: Will not burn. E.g. waterHealth code 1: Exposure would cause irritation but only minor residual injury. E.g. turpentineReactivity code 1: Normally stable, but can become unstable at elevated temperatures and pressures. E.g. calciumSpecial hazards (white): no code
0
1
1
Flash point nonflammable [1]
632 °C (1,170 °F; 905 K)
NIOSH (US health exposure limits):
PEL (Permissible)
None[1]
REL (Recommended)
TWA 1000 ppm (3500 mg/m3) ST 1250 ppm (4375 mg/m3)[1]
IDLH (Immediate danger)
N.D.[1]
Except where otherwise noted, data are given for materials in their standard state (at 25 °C [77 °F], 100 kPa).
N verify (what is YN ?)
Infobox references

Production and current applications

Worldwide production of R-22 in 2008 was about 800 Gg per year, up from about 450 Gg per year in 1998, with most production in developing countries.[2] R-22 use is increasing in developing countries, largely for air conditioning applications. Air conditioning sales are growing 20% annually in India and China.

R-22 is prepared from chloroform:

HCCl3 + 2 HF → HCF2Cl + 2 HCl

An important application of R-22 is as a precursor to tetrafluoroethylene. This conversion involves pyrolysis to give difluorocarbene, which dimerizes:[3]

2 CHClF2 → C2F4 + 2 HCl

The compound also yields difluorocarbene upon treatment with strong base and is used in the laboratory as a source of this reactive intermediate.

The pyrolysis of R-22 in the presence of chlorofluoromethane gives hexafluorobenzene.

Environmental effects

R-22 is often used as an alternative to the highly ozone-depleting CFC-11 and CFC-12, because of its relatively low ozone depletion potential of 0.055,[4] among the lowest for chlorine-containing haloalkanes. However, even this lower ozone depletion potential is no longer considered acceptable.

As an additional environmental concern, R-22 is a powerful greenhouse gas with a GWP equal to 1810 (which indicates 1810 times as powerful as carbon dioxide). Hydrofluorocarbons (HFCs) are often substituted for R-22 because of their lower ozone depletion potential, but these refrigerants often have a higher GWP. R-410A, for example, is often substituted, but has a GWP of 1725. Another substitute is R404A with a GWP of 3900. Other substitute refrigerants are available with low GWP. Ammonia (R717), popular in the early years of refrigeration, has a GWP of <1 and remains a popular substitute on fishing vessels. Ammonia’s toxicity and flammability limit its safe application.

Propane (R-290), is another example, and has a GWP of 3. Propane was the de facto refrigerant in systems smaller than industrial scale before the introduction of CFCs. The reputation of propane refrigerators as a fire hazard kept delivered ice and the ice box the overwhelming consumer choice despite its inconvenience and higher cost until safe CFC systems overcame the negative perceptions of refrigerators. Illegal to use as a refrigerant in the USA for decades, propane is now permitted for use in limited mass suitable for small refrigerators. It is not lawful to use in air conditioners, or larger refrigerators because of its flammability and potential for explosion.

Phaseout in the European Union

Since January 1, 2010, it has been illegal to use newly manufactured HCFCs to service refrigeration and air-conditioning equipment - only reclaimed and recycled HCFCs may be used. In practice this means that the gas has to be removed from the equipment before servicing and replaced afterwards, rather than refilling with new gas.

Since January 1, 2015, it has been illegal to use any HCFCs to service refrigeration and air-conditioning equipment; broken equipment that used HCFC refrigerants must be replaced with equipment that does not use them.[5]

Phaseout in the United States

R-22 has been mostly phased out in new equipment in the United States under the Montreal Protocol, and has been replaced by other refrigerants with lower ozone depletion potential such as propane (R-290), pentafluoroethane, R-134a (1,1,1,2-tetrafluoroethane), and blended mixtures of HFCs such as R-409A, R-410A, R-438A, and R-507A.[6][7] See refrigerant for specific components of the R-400 and R-500 HFC blends used to replace R-22.

  • Beginning January 1, 2004: The Montreal Protocol required the U.S. to reduce its consumption of HCFCs by 35% below the U.S. baseline cap. As of January 1, 2003, the United States Environmental Protection Agency banned production and import of HCFC-141b, the most ozone-destructive HCFC. This action allowed the United States to meet its obligations under the Montreal Protocol. The EPA was able to issue 100% of company baseline allowances for production and import of HCFC-22 and HCFC-142b.
  • Beginning January 1, 2010: The Montreal Protocol required the U.S. to reduce its consumption of HCFCs by 75% below the U.S. baseline. Allowance holders may only produce or import HCFC-22 to service existing equipment. Virgin R-22 may not be used in new equipment. As a result, heating, ventilation and air-conditioning (HVAC) system manufacturers may not produce new air conditioners and heat pumps containing R-22.
  • Beginning January 1, 2015: The Montreal Protocol required the U.S. to reduce its consumption of HCFCs by 90% below the U.S. baseline.
  • Beginning January 1, 2020: The Montreal Protocol requires the U.S. to reduce its consumption of HCFCs by 99.5% below the U.S. baseline. Refrigerant that has been recovered and recycled/reclaimed will be allowed beyond 2020 to service existing systems, but chemical manufacturers will no longer be able to produce R-22 to service existing air conditioners and heat pumps.

R-22, retrofit using substitute refrigerants

R-407A is for use in low- and medium-temp refrigeration. Uses a polyolester (POE) oil.

R-407C is for use in air conditioning. Uses a minimum of 20 percent POE oil.

R-407F is for use in medium- and low-temperature refrigeration applications (supermarkets, cold storage, and process refrigeration); direct expansion system design only. Uses a POE oil.

R-407H is for use in medium- and low-temperature refrigeration applications (supermarkets, cold storage, and process refrigeration); direct expansion system design only. Uses a POE oil.

R-421A is for use in “air conditioning split systems, heat pumps, supermarket pak systems, dairy chillers, reach-in storage, bakery applications, refrigerated transport, self-contained display cabinets, and walk-in coolers.” Uses mineral oil (MO), Alkylbenzene (AB), and POE.

R-422B is for use in low-, medium-, and high-temperature applications. It is not recommended for use in flooded applications.

R-422C is for use in medium- and low-temperature applications. The TXV power element will need to be changed to a 404A/507A element and critical seals (elastomers) may need to be replaced.

R-422D is for use in low-temp applications, and is mineral oil compatible.

R-424A is for use in air conditioning as well as medium-temp refrigeration temperature ranges of 20 to 50˚F. It works with MO, alkylbenzenes (AB), and POE oils.

R-427A is for use in air conditioning and refrigeration applications. It does not require all the mineral oil to be removed. It works with MO, AB, and POE oils.

R-434A is for use in water cooled and process chillers for air conditioning and medium- and low-temperature applications. It works with MO, AB, and POE oils.

R-438A (MO-99) is for use in low-, medium-, and high-temperature applications. It is compatible with all lubricants. [8]

R-458A is for use in air conditioning and refrigeration applications, without capacity or efficiency loss. Works with MO, AB, and POE oils. [9]

R-32 or HFC-32 (difluoromethane) is for use in air conditioning and refrigeration applications. it has zero ozone depletion potential (ODP) [2] and a global warming potential (GWP) index 675 times that of carbon dioxide.

Physical properties

Property Value
Density (ρ) at −69 °C (liquid) 1.49 g⋅cm−3
Density (ρ) at −41 °C (liquid) 1.413 g⋅cm−3
Density (ρ) at −41 °C (gas) 4.706 kg⋅m−3
Density (ρ) at 15 °C (gas) 3.66 kg⋅m−3
Specific gravity at 21 °C (gas) 3.08 (air is 1)
Specific volume (ν) at 21 °C (gas) 0.275 m3⋅kg−1
Density (ρ) at 15 °C (gas) 3.66 kg⋅m−3
Triple point temperature (Tt) −157.39 °C (115.76 K)
Critical temperature (Tc) 96.2 °C (369.3 K)
Critical pressure (pc) 4.936 MPa (49.36 bar)
Vapor pressure at 21.1 °C (pc) 0.9384 MPa (9.384 bar)[10]
Critical density (ρc) 6.1 mol⋅l−1
Latent heat of vaporization (lv) at boiling point (−40.7 °C) 233.95 kJ⋅kg−1
Heat capacity at constant pressure (Cp) at 30 °C (86 °F) 0.057 kJ.mol−1⋅K−1
Heat capacity at constant volume (Cv) at 30 °C (86 °F) 0.048 kJ⋅mol−1⋅K−1
Heat capacity ratio (γ) at 30 °C (86 °F) 1.178253
Compressibility factor (Z) at 15 °C 0.9831
Acentric factor (ω) 0.22082
Molecular dipole moment 1.458 D
Viscosity (η) at 0 °C 12.56 µPa⋅s (0.1256 cP)
Ozone depletion potential (ODP) 0.055 (CCl3F is 1)
Global warming potential (GWP) 1810 (CO2 is 1)

It has two allotropes: crystalline II below 59 K and crystalline I above 59 K and below 115.73 K.

Next diagram represents the pressure-enthalpy R22 properties, using Refprop 9.0 database, using the International Institute of Refrigeration reference.

Price history and availability

EPA's analysis indicated the amount of existing inventory was between 22,700t and 45,400t.[11][12]

Year 2010 2011 2012 2013 2014 2015–2019 2020
R-22 Virgin (t) 49,90045,40025,10025,60020,200TBD0
R-22 Recoupment (t) ------2,9502,950----
R-22 Total (t) 49,90045,40025,10028,60023,100----

TBD: To be determined [13]

In 2012 the EPA reduced the amount of R-22 by 45%, causing the price to rise by more than 300%. For 2013, the EPA has reduced the amount of R-22 by 29%.[14]

Refrigerants Price History
gollark: µhahahaha
gollark: Hmm, this is quite slow, initiating hacking into random IoT devices for more computing power.
gollark: Initiating osmarks.tk compute cluster™.
gollark: I heard it was quite large.
gollark: I'm aware of the APPLICABLE PLASTICITY project, but we don't seem to have had much success with current approaches.

References

  1. NIOSH Pocket Guide to Chemical Hazards. "#0124". National Institute for Occupational Safety and Health (NIOSH).
  2. Rosenthal, Elisabeth; Lehren, Andrew W. (June 20, 2012). "Relief in Every Window, but Global Worry Too". The New York Times. Archived from the original on June 21, 2012. Retrieved June 21, 2012.
  3. Günter Siegemund, Werner Schwertfeger, Andrew Feiring, Bruce Sart, Fred Behr, Herward Vogel, Blaine McKusick (2002). "Fluorine Compounds, Organic". Ullmann's Encyclopedia of Industrial Chemistry. Weinheim: Wiley-VCH. doi:10.1002/14356007.a11_349.CS1 maint: multiple names: authors list (link)
  4. The Montreal Protocol on Substances that Deplete the Ozone Layer. UNEP, 2000. ISBN 92-807-1888-6
  5. "Archived copy" (PDF). Archived (PDF) from the original on 2016-03-10. Retrieved 2015-09-08.CS1 maint: archived copy as title (link)
  6. EPA,OAR,OAP,SPD, US. "Phaseout of Ozone-Depleting Substances - US EPA". US EPA. Archived from the original on 17 January 2016. Retrieved 23 April 2018.CS1 maint: multiple names: authors list (link)
  7. "R22 Replacement refrigerant: ISCEON MO99 refrigerant". www2.dupont.com. Archived from the original on 16 May 2015. Retrieved 23 April 2018.
  8. Retrofit Refrigerants Archived 2013-06-24 at Archive.today
  9. https://www.federalregister.gov/documents/2017/07/21/2017-15379/protection-of-stratospheric-ozone-determination-33-for-significant-new-alternatives-policy-program
  10. "Frogen® R-22 - Frogen UK: Refrigerant and Cooling Specialists". frogen.co.uk. Archived from the original on 25 January 2017. Retrieved 23 April 2018.
  11. "Protection of Stratospheric Ozone: Adjustments to the Allowance System for Controlling HCFC Production, Import, and Export". federalregister.gov. 3 April 2013. Archived from the original on 4 March 2016. Retrieved 23 April 2018.
  12. "Protection of Stratospheric Ozone: Adjustments to the Allowance System for Controlling HCFC Production, Import, and Export". federalregister.gov. 3 April 2013. Archived from the original on 4 March 2016. Retrieved 23 April 2018.
  13. Virgin R-22 Allocations Final Rule (April 3, 2013)
  14. Specialty Cooling and Heating (Blog) January 22, 2013 Archived October 6, 2013, at the Wayback Machine
This article is issued from Wikipedia. The text is licensed under Creative Commons - Attribution - Sharealike. Additional terms may apply for the media files.