Malibu Hydro

Malibu Hydro System was designed to provide electricity to the Malibu Club in Canada. This hydro system starts from a high alpine lake where water is diverted from the lake through a steel penstock to a power house nearly 1,250 feet (380 m) below near the shore of Jervis Inlet. The flow of water turns a pelton wheel which is attached to a generator to create electricity. The electricity is then transmitted to camp by a submarine cable running under Jervis Inlet at a high voltage to reduce losses. Power is then distributed throughout camp on the existing and upgraded electrical system.[1]

Malibu Hydro Power
CountryCanada
LocationJervis Inlet, British Columbia
Coordinates50°8′40″N 123°52′40″W
StatusOperational
Owner(s)Malibu Club in Canada
Thermal power station
Turbine technologyMicro hydro
Power generation
Units operational580 kW Pelton
McCannel Creek Dam
Official nameMalibu Hydro Dam
LocationJervis Inlet, British Columbia, Canada
Dam and spillways
ImpoundsMcCannel Creek
Reservoir
CreatesMcCannel Lake

Sources

The hydro turbine is feed by a yearlong creek called McCannel Creek, which is directly across Jervis Inlet from Malibu. The creek's source is McCannel Lake, at an elevation of 2,600 feet (790 m). At the outlet of the lake, a dam was built to maintain the lake level and control the flow of the creek.

Malibu Hydro flow diagram

Weir (Item A)

A small weir type dam was built at the lake outlet, and, by limiting the discharge into the creek, aids in maintaining the lake level. The weir has a large pipe and valve in its base to pass the minimum 2 cubic feet per second (0.057 m3/s) required to maintain the creek. This is in addition to the water which will be spilled to create power.

Intake (Item B)

Water regulated at the lake will flow down the creek from the 2,300-foot (700 m) level to the 1,200-foot (370 m) level. Here a second weir was built across the creek that forms a large deep pool from which the 12-inch (300 mm) penstock draws water at a rate of up to 7 cu ft/s (0.20 m3/s).

Power House (Item C & D)

The power house contains the turbine, generator, and the necessary equipment to control and distribute the electricity for Malibu. It is located a short distance above the beach. The following diagram and table explains what happens once the water flow reaches the Power house (read the diagram right to left)

Item Process Function Measure Parameter
AJet & spear valveIntake water velocityPressure at valve in Penstock (PSI)10-620 PSI
BDeflectorDeflects water flow away from turbineAngle position of deflector (controlled by governor)0° - 90° Degrees
CTurbinePelton wheel turns in direction of water flowHow fast the turbine is turning (RPM)Fixed (rpm)
DShaftDistributes turning motion of turbine to the generatorHow fast the shaft is turningFixed (rpm)
EGeneratorGenerates the three phase AC electricityThe frequency output generated= 60 Hz
FGovernor (ELC)Maintains even load on Generator and flow on turbineFrequency sample either from shaft, or generator, or switch gear= 60 Hz
GSwitch gearBreakers to break up flow if necessaryHalts flow of electricity if too high---
HTransformerSteps the voltage up to be transferred to camp---600 V – 14000 V

Power Line (Item E)

Transformers at the hydro generator raise 600 volts to 15,000 volts for transmission. Power is transmitted across Jervis inlet, a distance of two miles (3 km) via an underwater power line consisting of three parallel conductors. On the Malibu side of the inlet, a transformer steps the 15,000 volts down to 120 and 208 volts for use at the camp.

History

It began installation in 2005.

gollark: Technically, I own the sun and will invoice heavy users.
gollark: As far as I know, no country technically has laws specifically about cognitohazards.
gollark: No, those are twisted-pair.
gollark: I run my WiFi over coaxial cables to prevent eavesdropping.
gollark: It's a shame we've lost all this possibly cool™ information to things.

References

This article is issued from Wikipedia. The text is licensed under Creative Commons - Attribution - Sharealike. Additional terms may apply for the media files.